Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.5.1.4 x Install and verify cab floor covering. 8/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Verify ride/leveling quality. 8/14/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space (2nd landing) lighting shall be atleast 19 fc. 8/14/2025
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 2.9.1 x Top of hoistway hoisting beam needs capacity labeled. 8/14/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk/fill holes and voids in hoistway walls. 8/14/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Top of hoistway light switch box is missing hole/knockout cover. 8/14/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc. 8/14/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Pit sump pump "Oil Tector" shall be relocated outside of pit area. 8/14/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27 x x Top of hoistway smoke detector shall be within 12" of ceiling. 8/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test top and bottom overtravel measurements, 3D edge, remainder of pit equipment and clearances. 8/14/2025