A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine space (2nd landing) lighting shall be atleast 19 fc.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
2.9.1
|
x
|
|
Top of hoistway hoisting beam needs capacity labeled.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk/fill holes and voids in hoistway walls.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
3.8
|
x
|
|
Top of hoistway light switch box is missing hole/knockout cover.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall be at least 10fc.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
3.8
|
x
|
|
Pit sump pump "Oil Tector" shall be relocated outside of pit area.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27
|
x
|
x
|
Top of hoistway smoke detector shall be within 12" of ceiling.
|
8/14/2025
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.5.1.4
|
x
|
|
Install and verify cab floor covering.
|
8/14/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Verify ride/leveling quality.
|
8/14/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test top and bottom overtravel measurements, 3D edge, remainder of pit equipment and clearances.
|
8/14/2025
|