A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
x
|
|
Replace missing "Do not use elevator in case of fire" signage on multiple floors.
|
9/23/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Mainline disconnecting means (2) shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply in event of shunt or manual disconnect.
|
8/28/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Landing lighting at LL not installed. Install and verify greater than 5fc.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine space shall have GFCI outlet. Currently standard outlet.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine space lighting shall not be less than 19fc at floor.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fill hoistway fire/smoke penetrations with proper material.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Top of hoistway has multiple screws penetrating ceiling, creating hazard for cartop.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Top of hoistway angle brackets attached to ceiling; all anchor bolts are loose.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fill pit fire/smoke penetrations with proper materials (fire caulk).
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Top of hoistway exhaust fan shall stop operation in the event of FAID activation.
|
8/28/2025
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
x
|
|
Landing door sill at LL has large gap. Shall be filled and flush.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Replace pit sump cover with appropriate cover, removable and allows for proper drainage (currently 1/2" plate steel, lacking proper drainage flow and not serviceable)
|
8/28/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Verify sump pump capable of 3000GPH per elevator. Unable to move cover to verify.
|
9/23/2025
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Runby exceeds OEM spec of 7" from buffer to strike plate.
|
8/28/2025
|