Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 x Replace missing "Do not use elevator in case of fire" signage on multiple floors. 9/23/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space shall have GFCI outlet. Currently standard outlet. 9/23/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting shall not be less than 19fc at floor. 9/23/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill hoistway fire/smoke penetrations with proper material. 9/23/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Top of hoistway has multiple screws penetrating ceiling, creating hazard for cartop. 9/23/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Top of hoistway angle brackets attached to ceiling; all anchor bolts are loose. 9/23/2025
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x Landing door sill at LL has large gap. Shall be filled and flush. 9/23/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill pit fire/smoke penetrations with proper materials (fire caulk). 9/23/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Verify sump pump capable of 3000GPH per elevator. Unable to move cover to verify. 9/23/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Replace pit sump cover with appropriate cover, removable and allows for proper drainage (currently 1/2" plate steel, lacking proper drainage flow and not serviceable) 8/28/2025
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Runby exceeds OEM spec of 7" from buffer to strike plate. 8/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway exhaust fan shall stop operation in the event of FAID activation. 8/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Mainline disconnecting means (2) shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply in event of shunt or manual disconnect. 8/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Landing lighting at LL not installed. Install and verify greater than 5fc. 9/23/2025