Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Emergency power shall be tesed.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Emergency power operation shall be tested. 12/19/2025
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Car door restrictor shall work as designed. 12/19/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications x Communication loss buzzer reset keyswitch does not work 12/19/2025
A17.1-2016 : Elevators 1.8 - Door closing force 8.10.2.2.1(h) x Door closing force shall be tested. 12/19/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.3.2.2(r) x Lighting disconnect is obstructed by main disconnects. (see also NEC/NFPA 110.26) 12/19/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.3.2(s) x Mainline and lighting disconnects to be labeled for function. 12/19/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Fire caulk smoke/fire penetrations. 12/19/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) x Compliant MCP (with all documentation including evac procedures, wiring diagrams, ect.) needed. 12/19/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) x Fire extinguisher shall be permanently mounted adjacent to the door. 12/19/2025
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Hoistway acess swtiches (top and bottom) shall not be more than 12" from the entrance frames. Currently mounted on hall call station, approximately 42" from entrance frame. 12/19/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 x Pit lighting shall not be less than10fc at the floor level. (Currently 4fc) 12/19/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Fire service phase I and phase II shall be tested. 12/19/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x All FAID shall be tested for functionality and reacall (heats, shunts, smokes). Smoke detector installation incomplete but observed 2nd floor smoke is less than 36" from HVAC vent. 12/19/2025