A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Emergency power shall be tesed.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Emergency power operation shall be tested.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
x
|
|
Car door restrictor shall work as designed.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.19.15 Emergency Communications
|
x
|
|
Communication loss buzzer reset keyswitch does not work
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.10.2.2.1(h)
|
x
|
|
Door closing force shall be tested.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.3.2.2(r)
|
x
|
|
Lighting disconnect is obstructed by main disconnects. (see also NEC/NFPA 110.26)
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.3.2(s)
|
x
|
|
Mainline and lighting disconnects to be labeled for function.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Fire caulk smoke/fire penetrations.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
x
|
|
Compliant MCP (with all documentation including evac procedures, wiring diagrams, ect.) needed.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.2.2.2(l)
|
x
|
|
Fire extinguisher shall be permanently mounted adjacent to the door.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
x
|
|
Hoistway acess swtiches (top and bottom) shall not be more than 12" from the entrance frames. Currently mounted on hall call station, approximately 42" from entrance frame.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
x
|
|
Pit lighting shall not be less than10fc at the floor level. (Currently 4fc)
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Fire service phase I and phase II shall be tested.
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
All FAID shall be tested for functionality and reacall (heats, shunts, smokes). Smoke detector installation incomplete but observed 2nd floor smoke is less than 36" from HVAC vent.
|
12/19/2025
|