Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine Space shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) MCP, including PM records and monthly Fire service test log, not being properly documented . Logs blank.
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 oistways shall have floor numbers, not less than (4 in.) in height, on the hoistway side of the doors. Floors G1 and G2 have hoistway numbers of UP and LP. All floors shall be consistently numbered.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Retractable ladders shall be capable of being extended, mechanically secured and unsecured,and retracted from the access door, and (a) the force(s) required to extend a retractable ladder from the fully retracted position to the extended and mechanically secured position shall not exceed 220 N(50 lbf). Ladder is jammed and was unable to extend.