A17.1-2016 : Elevators
|
1.3 - Operating control devices
|
2.26.1
|
|
|
Labeling for floor G1 on Car Operating Panel shows "UP". Label/designation shall be consistent.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine Space shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Compliant/Required Documentation shall be kept in equipment room(neat/organized) including MCP, Wiring Diagrams, PM log, Callback log, Fire Service Testing log, & Evacuation procedures. No MCP documentations could be found.
|
|
|
A17.1-2016 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
Hoistways shall have floor numbers, not less than (4 in.) in height, on the hoistway side of the doors. Floors G1 and G2 have hoistway numbers of UP and LP. All floors shall be consistently numbered.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-WAY COMMUNICATION DEVICE SHALL WORK PROPERLY. Agent stated line had a "Loud buzzing noise" then was unable to hear caller ask questions.
|
|