A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.1 x Counterweight Runby(7.5") exceeds OEM maximum allowable runby(6.5"), as posted on Counterweight Runby Data Plate. Adjust for compliance
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine Space shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) MCP, including PM records and monthly Fire service test log, not being properly documented . Logs blank.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self-closing and self-locking. Stationary door latch is jammed/broken.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x 2-WAY COMMUNICATION DEVICE SHALL WORK. "Rescue phone", located at G1 Lobby does not work.
A17.1-2016 : Elevators 1.12 - Car enclosure 2.14.1.9 Car Operating Panel, lower access door for switches, is broken and shall be repaired.