A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-WAY COMMUNICATION DEVICE SHALL WORK. "Rescue phone", located at G1 Lobby does not work.
|
|
|
A17.1-2016 : Elevators
|
1.12 - Car enclosure
|
2.14.1.9
|
|
|
Car Operating Panel, lower access door for switches, is broken and shall be repaired.
|
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door shall be self-closing and self-locking. Stationary door latch is jammed/broken.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine Space shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
MCP, including PM records and monthly Fire service test log, not being properly documented . Logs blank.
|
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.1
|
x
|
|
Counterweight Runby(7.5") exceeds OEM maximum allowable runby(6.5"), as posted on Counterweight Runby Data Plate. Adjust for compliance
|
|