A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
x
|
|
Machine room door shall have same fire rating as room/hoistway.
|
|
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means.
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room lighting shall not be less than 200lux/19fc at floor.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Ladder rung centers shall not be less than 4" from pit wall.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Sump shall have the capacity to remove a minimum of 11.4m3/h per elevator.
|
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.3.2(s)
|
x
|
|
Lighting disconnect has neutral fused and fusing shall be 15A, currently 30A.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.7.2.27.4
|
x
|
|
Lighting disconnect has infringed workspace clearance.
|
|