Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have same fire rating as room/hoistway.
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room lighting shall not be less than 200lux/19fc at floor.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Ladder rung centers shall not be less than 4" from pit wall.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Sump shall have the capacity to remove a minimum of 11.4m3/h per elevator.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.3.2(s) x Lighting disconnect has neutral fused and fusing shall be 15A, currently 30A.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.7.2.27.4 x Lighting disconnect has infringed workspace clearance.