Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x 2.8.3.3.2 - Machine space heat detector activated but failed to trip shunt. 8/21/2025
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation x Determine if unit is requires Earthquake Detections ("Ring & String") based on Fp>0.5Wp and Zone 3 requirements. If not required, wiring diagrams/power data sheet shall be updated and data provided to inspector. If required, install detections and reinspect. Unit is located in Seismic Zone D, Importance 1. 8/21/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Install large "Fire Extinguisher" signage to direct to fire extinguisher around corner of machine space on second floor. 8/21/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control n/a x Main line disconnect (480 volt) obstructed. Must have a minimum of 48" clearance to front of disconnect. Relocate without obstructing lighting disconnect. See also NEC 110.26. 8/21/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall not be less than 10fc at the pit floor. 8/21/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x Remove and or relocate "Oil Tector" control box from pit area. 8/21/2025
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 x Replace missing "Do not use elevator in case of fire" signage on multiple floors. 8/21/2025