Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit sump pump is required and shall have the capacity to remove a minimum of 11.4 m3/h (3.000gal/h) per elevator (allowing for head pressure resulting from discharge piping height). Pump installed currently ois zoellerM53 = 2600 gal/h. 12/2/2025