A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump pump is required and shall have the capacity to remove a minimum of 11.4 m3/h (3.000gal/h) per elevator (allowing for head pressure resulting from discharge piping height). Pump installed currently ois zoellerM53 = 2600 gal/h.
|
12/2/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump pump discharge piping not connected to building pumbling, discharges onto the floor in the room next to the hoistway.
|
12/2/2025
|