Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x sump pump doesnt have cover.. need to add and make flush w pit floor 7/1/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x unit needs fire extinguisher located near top floor control space 7/1/2025
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.1 x phone is not tagged to identify caller location 7/1/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x missing electrical box cover above bottom floor in shaft 7/1/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x MRL unit has heat sensor for sprinkler beyond 24" need to relocate sensor or move sprinkler head 7/1/2025