Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation x 1st floor smoke detector installed at less than 36" of HVAC register. 2/23/2026
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation x 2nd floor Heat detectors shall trigger Shunt Trip Breaker. 2/23/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint. 2/23/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x levators that are equipped to operate on Emergency Power shall be tested operating on Em Power. 2/23/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit Sump Pump is required and shall have the capacity to remove a minimum of 11.4 m3/h (3,000 gal/h) per elevator (allowing for head pressure resulting from discharge piping height of 19ft). 2/23/2026