A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Standby power/Emergency generator system/Add-a-phase system faults with full load capacity test is attempted.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Standby power system does not send pre-warn signal before swapping back to utility power.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication does not work, line is dead.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
Phase converter shall have a disconnecting means that is readily accessible and located in sight of the phase converter in the machine room
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Machine room lighting is less than 19ftc at floor level.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Wall penetrations & gaps to be properly fire-caulked
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Wall penetrations & gaps to be properly fire-caulked.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Pit ladder rungs shall have at least 4" clearance to wall with out obstruction. (conduit infringes top foot rung)
|
10/30/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Wall penetrations & gaps to be properly fire-caulked.
|
10/30/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Sump discharge piping shall be fire-resistant.
|
10/30/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Lighting is less than 10ftc at the front of pit (measured 8ftc)
|
10/30/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
There is a drain pipe dumping into sump. Cannot introduce liquids into pit/hoistway
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
GFI and sump outlets are less than 48" off pit floor, therefore shall have water-resistanct boxes and covers.
|
11/18/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
4X4 electrical box has a hole that exposes wire.
|
11/18/2025
|