Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Standby power/Emergency generator system/Add-a-phase system faults with full load capacity test is attempted. 11/18/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Standby power system does not send pre-warn signal before swapping back to utility power. 11/18/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication does not work, line is dead. 11/18/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x Phase converter shall have a disconnecting means that is readily accessible and located in sight of the phase converter in the machine room 11/18/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Machine room lighting is less than 19ftc at floor level. 11/18/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Wall penetrations & gaps to be properly fire-caulked 11/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Wall penetrations & gaps to be properly fire-caulked. 11/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Pit ladder rungs shall have at least 4" clearance to wall with out obstruction. (conduit infringes top foot rung) 10/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Wall penetrations & gaps to be properly fire-caulked. 10/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Sump discharge piping shall be fire-resistant. 10/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x Lighting is less than 10ftc at the front of pit (measured 8ftc) 10/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x There is a drain pipe dumping into sump. Cannot introduce liquids into pit/hoistway 11/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x GFI and sump outlets are less than 48" off pit floor, therefore shall have water-resistanct boxes and covers. 11/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x 4X4 electrical box has a hole that exposes wire. 11/18/2025