Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No the inspecion tag on the machine room fire extinguisher is expired, have the machine room fire extinguisher inspected and tagged 3/12/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No the elevator emergency phone did not work, provide a working phone line to the elevator controller 3/12/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No provide a record of findings for firefighters' operation 12/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No does not have a Maintenance Control Program (MCP) book in the machine room 10/27/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No monthly fire service test log is not being filled out monthly 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No emergency phone did not connect to answering service, rang a couple of times then hangs up 8/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide fire extinguisher in the machine room