ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.8 - Safeties and Speed Governors
|
2.8
|
x
|
x
|
Unit's safeties shall be tested with proper weight.
|
10/8/2025
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.6 - Platforms
|
2.6.6.1
|
x
|
|
Unit shall have a minimum of 5fc of lighting within the unit's enclosure.
|
10/8/2025
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.11 - Emergency Signals
|
2.11.2
|
x
|
|
Unit is equipped with phone that shall establish 2-way communication and shall operate on auxiliary power.
|
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.11 - Emergency Signals
|
2.11.2
|
x
|
|
Unit is equipped with phone that shall establish 2-way communication and shall operate on auxiliary power.
|
10/8/2025
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
2.11 - Emergency Signals
|
2.11.1
|
x
|
|
Emergency light and alarm bell shall operate when power is lost to the unit.
|
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements
|
10.1.3 Acceptance Inspections and Tests
|
x
|
|
Unit shall be hard-wired to a properly labeled disconnect that is visible from the unit.
|
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements
|
10.1.3 Acceptance Inspections and Tests
|
x
|
|
Unit shall be hard-wired to a properly labeled disconnect that is visible from the unit.
|
10/8/2025
|
|
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts
|
10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements
|
10.1.3 Acceptance Inspections and Tests
|
x
|
|
Unit's hydraulic pressure shall be recorded.
|
10/8/2025
|