Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 2.8 - Safeties and Speed Governors 2.8 x x Unit's safeties shall be tested with proper weight. 10/8/2025
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements 10.1.3 Acceptance Inspections and Tests x Unit's hydraulic pressure shall be recorded. 10/8/2025
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 2.6 - Platforms 2.6.6.1 x Unit shall have a minimum of 5fc of lighting within the unit's enclosure. 10/8/2025
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements 10.1.3 Acceptance Inspections and Tests x Unit shall be hard-wired to a properly labeled disconnect that is visible from the unit.
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 10.1 Routine, Periodic, and Acceptance Inspections and Test General Requirements 10.1.3 Acceptance Inspections and Tests x Unit shall be hard-wired to a properly labeled disconnect that is visible from the unit. 10/8/2025
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 2.11 - Emergency Signals 2.11.2 x Unit is equipped with phone that shall establish 2-way communication and shall operate on auxiliary power. 10/8/2025
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 2.11 - Emergency Signals 2.11.2 x Unit is equipped with phone that shall establish 2-way communication and shall operate on auxiliary power.
ASME A18.1-2014 : Platform Lifts & Stairway Chairlifts 2.11 - Emergency Signals 2.11.1 x Emergency light and alarm bell shall operate when power is lost to the unit.