Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Smoke detectors still need to be checked, tech could not get them to work.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Second floor entrance to elevator lighting shall be 19 fc since it is considered a machine space.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x When walls around entrance to elevators are complete, all required signage shall be installed.