A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
SEAL ALL VOIDS IN HOISTWAY WALLS
|
1/30/2026
|
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
2.13.4.2.3
|
x
|
|
CLOSING FORCE IS >30 LBS. ADJUST TO <3O LBS
|
1/30/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
COULD NOT TEST SMOKE ALARMS AS THE ALARM COMPANY DID NOT HAVE IT FINISHED
|
1/30/2026
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
HOISTWAY SMOKE ALARM WIRES MUST BE IN CONDUIT WHERE THEY PENETRATE A WALL
|
1/30/2026
|