Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Elevators that are equipped to operate on emergency power shall be tested while operating on emergency power. 3/23/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.10.2.2.2(i) x Machine space shall have GFCI outlet. Convert sstandard outlet approximately 8ft to the left of the elevator doors to GFCI. 3/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) x Lighting disconnect shall be labeled with elevator number, location of feeder breakers, and function. 3/23/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x Lighting disconnect shall be an enclosed, externally operable, lockable, fused type. 3/23/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.3.2(s) x Verify mainline disconnects are fused and fuses are OEM compliant. 3/23/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Fire caulk/fill holes and voids in the hoistway walls, included but not limited to those with red paint. 3/23/2026