A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.3.2(s)
|
x
|
|
Verify mainline disconnects are fused and fuses are OEM compliant.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.10.2.2.2(i)
|
x
|
|
Machine space shall have GFCI outlet. Convert sstandard outlet approximately 8ft to the left of the elevator doors to GFCI.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
8.10.2.2.2(o)
|
x
|
|
Lighting disconnect shall be labeled with elevator number, location of feeder breakers, and function.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
Lighting disconnect shall be an enclosed, externally operable, lockable, fused type.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Fire caulk/fill holes and voids in the hoistway walls, included but not limited to those with red paint.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested while operating on emergency power.
|
3/23/2026
|