Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 6/25/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Elevator will not go to alternate level on Firefighters' Service Phase I recall when Floor 1 smoke detector is triggered. Currently recalls to Floor 1. 6/25/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) x x Driving machine brake failed during Category 1 test. 9/17/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Brake failed before all Category 1 tests/inspection could be performed. 9/17/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 6/21/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power indicator jewel in fire command room not working. 3/24/2023