MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Elevator will not go to alternate level on Firefighters' Service Phase I recall when Floor 1 smoke detector is triggered. Currently recalls to Floor 1.
|
9/17/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing but was not tested.
|
6/21/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing but was not tested.
|
9/17/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Means of Communication (Red Tag)
|
|
|
Two-way communication (phone) not working when 110V removed.
|
6/15/2022
|