Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete: ALL CAT5 weight tests (Test GOV pullout/pullthru, Spin GOV, safeties, UM up and Down, 125%, and 100% safety set, slide, etc.).
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Mainline and Lighting disconnect shall be labeled with Elevator number, location of feeder breakers, and function
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) Yes No Lighting Disconnect shall be fused at 15A(currently 20A) and the neutral shall not be fused.
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.10.2.2.2(u) Yes No Top of Hoistway Beam shall have capacity labeling.
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint.
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems Yes No Install missing "Car 1" and "Star of Life" signage on each door frame.
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems Yes No Replace missing "Do not use elevator in case of fire" Signage on multiple floors.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Pit Sump Pump is required and shall have the capacity to remove a minimum of 11.4 m3/h (3,000 gal/h) per elevator (allowing for head pressure resulting from discharge piping height(5ft)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Relocation 4th Floor Smoke Detector, cannot be within 36" of HVAC venting.