Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 There are voids/holes in the shaft made by installing new ventilation without guards. 9/6/2022
MO Minimum : Elevators (A) - Hoistways (A)13 There are voids/holes in the shaft made by installing new ventilation without guards.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Top final limit switch functions, but elevator cannot reach it. Ropes need to be shortened. 6/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power existing but was not tested. 6/21/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 6/25/2020
conversion conversion n/a Observed car emergency lighting not working. 6/25/2019