MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
There are voids/holes in the shaft made by installing new ventilation without guards.
|
9/6/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
There are voids/holes in the shaft made by installing new ventilation without guards.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Elevator doors will not open when recalled to alternate landing on Firefighters' Service. Rear door.
|
6/25/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency power existing but was not tested.
|
6/21/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
When transferred to standby power, elevator would not return to main floor or manually transfer if Elevator 3 mainline disconnect was off.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing but was not tested.
|
6/25/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door restrictor not working. Front car door.
|
2/28/2019
|
conversion
|
conversion
|
n/a
|
|
|
Most recent operating certificate not framed in machine room.
|
2/28/2019
|