MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Sprinkler head has been added in machine room - needs heat detector w/ shunt trip.
|
6/15/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Sprinkler head has been added in machine room - needs heat detector w/ shunt trip.
|
6/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency power is existing but was not tested.
|
6/21/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication in car not working properly.
|
9/1/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
When transferred to standby power, elevator would not return to main floor or manually transfer if Elevator 3 mainline disconnect was off.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Firefighters' Service initiating devices (smokes) bypassed. Remove plastic bags from smokes in machine room and top floor landing.
|
6/24/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Two-way communication (phone) failed test when 110V removed.
|
6/24/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing but was not tested.
|
6/24/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing but was not tested.
|
12/4/2020
|