Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Two-way communication (phone) failed test when 110V removed. 6/24/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 6/24/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 12/4/2020
MO Minimum : Elevators (H) - Machine Rooms (H)7 Sprinkler head has been added in machine room - needs heat detector w/ shunt trip. 6/15/2022
MO Minimum : Elevators (H) - Machine Rooms (H)7 Sprinkler head has been added in machine room - needs heat detector w/ shunt trip. 6/15/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x Firefighters' Service initiating devices (smokes) bypassed. Remove plastic bags from smokes in machine room and top floor landing. 6/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication in car not working properly. 9/1/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power is existing but was not tested. 6/21/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x When transferred to standby power, elevator would not return to main floor or manually transfer if Elevator 3 mainline disconnect was off.