Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)6 Hoistway door panels at bottom landing can be pulled apart over 2" at the bottom section of the door while the doors are closed/locked. 4/13/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Hoistway door interlocks shall be maintained. Interlocks are breaking electrically before mechanically at Floors 1(R), 2, 3, 7, 8, 9.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power was existing but was not tested. 1/27/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency Power existing but was not tested. 1/28/2021