Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No All fire service aspects shall be checked when repaired and complete 7/14/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency back up battery system shall be checked when repaired. 7/14/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No All governor and safety test shall be done. 7/14/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No All covers and signage shall be installed 7/14/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Lighting shall not be less than 200lux/19fc at floor in front of controller. 7/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Lighting and Mainline disconnects, in Electrical Closet, shall be labeled with location of feeder breakers, and function 7/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Lighting and Mainline breakers, in 4th Floor Elevator Testing Panel, shall be labeled with location of feeder breakers, and function 7/23/2026
A17.1-2016 : Elevators 9.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.5 Yes No The seismic still needs to be checked. 7/14/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation Yes No MCP's shall be left onsite. 7/14/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls Yes No Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint. 7/23/2026