Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls Yes No Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint. 7/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Lighting and Mainline disconnects, in Electrical Closet, shall be labeled with location of feeder breakers, and function 7/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Lighting and Mainline breakers, in 4th Floor Elevator Testing Panel, shall be labeled with location of feeder breakers, and function 7/23/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Lighting shall not be less than 200lux/19fc at floor in front of controller. 7/23/2026