Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x 2.8.3.3.2(b) - 2nd Floor Machine Space has 2 sprinklers, requiring 2 heat detectors for proper activation of Shunt. 2/27/2026
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x 2nd Floor Machine Space shall have proper Fire Extinguisher and shall have current monthly/annual test tag. 2/27/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint. 2/27/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x Lighting Disconnect shall be fused at 15amp, currently fused at 20amp. 2/27/2026
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of Hoistway overhead water pipe to be removed. Water piping is not used in conjunction with the operation of the elevator. If Sprinkler is added, must conform to NFPA 13 as well. 2/27/2026