Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Door restrictor not working. 2/27/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire Extinguishers out of date.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b HVAC in machine room was broken.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication and emergency lighting not working when 110V is removed. 6/6/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Observed emergency light not working on battery backup 6/11/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency power is existing but was not tested. 6/11/2020