Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Sump pump not correctly installed required float device to activate. 8/28/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Sump pump rate of ?ow unknown shall be 3000 gallons per hour. 8/28/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Sump pump rate of flow shall be 3000 gallons per hour. The amount of rise shall be considered into this flow rate.
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.10.2.2.1(o) Yes No Sinage required on the machine room door.
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.10.2.2.1(o) Yes No Sinage required on the machine room door. 8/28/2026