Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Door gibs not fastened in accordance with manufacturer requirements. Gib loose car door panel.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b HVAC was not working in machine room.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher out of date.
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Hoistway door closer not working correctly at Floor 6.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication and emergency lighting not working when 110V is removed. 6/6/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension cables undersized. 5/23/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Observed emergency light not working on battery back up. 6/11/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency power existing but not tested. 6/11/2020