MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Suspension cables undersized.
|
5/23/2024
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
100.5
|
|
|
101.5 HVAC not working in machine room.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher out of date.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2 way communication and emergency lighting not working when 110V is removed.
|
6/9/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In-car alarm bell not ringing when 110V is removed.
|
6/8/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Emergency power existing but not tested.
|
6/11/2020
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
211.1(a)(3) Observed emergency light not working as required on battery backup.
|
6/11/2020
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency power testing failed on this elevator
|
6/9/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
A17.1 1994 211.2 - Tripped limit board in down direction between 2-1 and went out of service during emergency power test.
|
6/8/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
cCar occasionally washes out on emergency power, however it does recover.
|
5/23/2024
|