Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ANSI/ASSP A10.4-2016 : Hoists 16.7 - Car Frame and Platform Connections 16.7 Yes No Hinges @25 needs more than 1 screw on frame side. 6/2/2026
ANSI/ASSP A10.4-2016 : Hoists 5.6 - Landings 5.6 Yes No Multiple Hoistway landing door sills need additional screws for proper support. (15th floor and above) 6/2/2026
ANSI/ASSP A10.4-2016 : Hoists 5.6 - Landings 5.6 Yes No Need to erect walls/barriers at 2nd landing to restrict contact of at least 30" from lift. (full height walls, standard strength) 6/2/2026
ANSI/ASSP A10.4-2016 : Hoists 5.6 - Landings 5.6 Yes No Cover landing windows to restrict contact of at least 30" from lift. To include restriction of opening windows. Affecting at least 4,7,10,14,17,20,23, and 27 6/2/2026
ANSI/ASSP A10.4-2016 : Hoists 5.1 - Tower or Mast Construction 5.1.1 Yes No Multiple bent/damaged cross-braces(lacing). Repair/replace to OEM spec. 6/2/2026