Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested while operating on Emergency Power. 3/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 Yes No Lighting disconnect shall be labeled with Elevator number, location of feeder breakers, and function(example: "Elevator Lighting Disconnect"). 3/23/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) Yes No Lighting disconnect shall be an enclosed, externally operable, lockable, fused type. See also NEC/NFPA70-620.53 3/23/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) Yes No Verify Mainline Disconnects are fused and fuses are OEM compliant. See also NEC/NFPA70-620.51(1) 3/23/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Machine space lighting shall not be less than 200lux/19fc at floor in front of controller(currently 12fc) and shall not be controlled by a motion sensor switch. 3/23/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No 2.8.2.1 Machine Space shall have GFCI outlet. 3/23/2026
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No 2.7.1.1.1 Machine Space - Fire caulk around Fire Alarm boxes/covers to maintain Wall Fire Rating. 3/23/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls Yes No Fire caulk/fill holes and voids in Hoistway walls, included but not limited to those marked with Red Paint. 3/23/2026