A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested while operating on Emergency Power.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
Yes
|
No
|
Machine space lighting shall not be less than 200lux/19fc at floor in front of controller(currently 12fc) and shall not be controlled by a motion sensor switch.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
2.8.2.1 Machine Space shall have GFCI outlet.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
Yes
|
No
|
2.7.1.1.1 Machine Space - Fire caulk around Fire Alarm boxes/covers to maintain Wall Fire Rating.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
Yes
|
No
|
Lighting disconnect shall be labeled with Elevator number, location of feeder breakers, and function(example: "Elevator Lighting Disconnect").
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
Yes
|
No
|
Lighting disconnect shall be an enclosed, externally operable, lockable, fused type. See also NEC/NFPA70-620.53
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
Yes
|
No
|
Verify Mainline Disconnects are fused and fuses are OEM compliant. See also NEC/NFPA70-620.51(1)
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
Yes
|
No
|
Fire caulk/fill holes and voids in Hoistway walls, included but not limited to those marked with Red Paint.
|
3/23/2026
|