Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Elevators that are equipped to operate on Emergency Power shall be tested while operating on Emergency Power. 3/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.3.2(r) x Lighting disconnect shall be an enclosed, externally operable, lockable, fused type. See also NEC/NFPA70-620.53 3/23/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 x Lighting disconnect shall be labeled with Elevator number, location of feeder breakers, and function(example: "Elevator Lighting Disconnect"). 3/23/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) x Verify Mainline Disconnects are fused and fuses are OEM compliant. See also NEC/NFPA70-620.51(1) 3/23/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x 2.8.2.1 Machine Space shall have GFCI outlet. 3/23/2026
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Machine Space shall have proper Fire Extinguisher. Closest Extinguisher is >36' from controller. 3/23/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Fire caulk/fill holes and voids in Hoistway walls, included but not limited to those marked with Red Paint. 3/23/2026
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 x Hoistway doors shall be self-closing, 2nd Floor door dragging due to concrete/mortar on door sill. 3/23/2026