A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Elevators that are equipped to operate on Emergency Power shall be tested while operating on Emergency Power.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
8.10.2.3.2(r)
|
x
|
|
Lighting disconnect shall be an enclosed, externally operable, lockable, fused type. See also NEC/NFPA70-620.53
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Lighting disconnect shall be labeled with Elevator number, location of feeder breakers, and function(example: "Elevator Lighting Disconnect").
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
x
|
|
Verify Mainline Disconnects are fused and fuses are OEM compliant. See also NEC/NFPA70-620.51(1)
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
2.8.2.1 Machine Space shall have GFCI outlet.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Machine Space shall have proper Fire Extinguisher. Closest Extinguisher is >36' from controller.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Fire caulk/fill holes and voids in Hoistway walls, included but not limited to those marked with Red Paint.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
x
|
|
Hoistway doors shall be self-closing, 2nd Floor door dragging due to concrete/mortar on door sill.
|