A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
x
|
x
|
2.27.3.2.1(c) Pit shall also have a smoke detector to initiate recall before Heat detector initiates shunt trip.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
8.10.3.2.6
|
x
|
x
|
All devices and functions associated with Elevator will be tested.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
2.8.3.3.2(b) Pit heat is greater than 24" from sprinkler.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Lighting shall not be less than 200lux/19fc at floor in front of controller.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine space lighting disconnect fuse shall be 15A, currently 10A
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine space lighting disconnect shall not fuse the neutral wire.
|
3/23/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work properly.
|
3/23/2026
|