Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Emergency Recall operation by Fire Alarm Initiating Devices shall be tested for acceptance.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x 2.8.2.3.4 All electrical below 48" from pit floor shall be designed for "wet locations" (weather resistant).(outlets shall have weather resistant(in-use) covers or relocate to above 48".
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Pit sump cover shall be able to safely withstand the weight of a worker with minimal deflection and allow proper water flow to sump.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Machine Room shall have proper Fire Extinguisher.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Lighting Disconnect is obstructed / Not Co-Planar with surrounding disconnects.
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 x Mainline and Lighting disconnect shall be labeled with function and feeder breaker info.
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 x Landing sills to be substantially flush with the floor surface of the elevator landings. Flooring is not fully installed and flush to hoistway sills.