Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 Yes No Landing sills to be substantially flush with the floor surface of the elevator landings. Flooring is not fully installed and flush to hoistway sills. 4/7/2026
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No Machine Room shall have proper Fire Extinguisher. 4/7/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 Yes No Mainline and Lighting disconnect shall be labeled with function and feeder breaker info. 4/7/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 Yes No Lighting Disconnect is obstructed / Not Co-Planar with surrounding disconnects. 4/7/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No 2.8.2.3.4 All electrical below 48" from pit floor shall be designed for "wet locations" (weather resistant).(outlets shall have weather resistant(in-use) covers or relocate to above 48". 4/7/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Yes No Pit sump cover shall be able to safely withstand the weight of a worker with minimal deflection and allow proper water flow to sump. 4/7/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Emergency Recall operation by Fire Alarm Initiating Devices shall be tested for acceptance. 4/7/2026