A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
2.8.2.3.4 All electrical below 48" from pit floor shall be designed for "wet locations" (weather resistant).(outlets shall have weather resistant(in-use) covers or relocate to above 48".
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Emergency Recall operation by Fire Alarm Initiating Devices shall be tested for acceptance.
|
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
Landing sills to be substantially flush with the floor surface of the elevator landings. Flooring is not fully installed and flush to hoistway sills.
|
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Lighting Disconnect is obstructed / Not Co-Planar with surrounding disconnects.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Machine Room shall have proper Fire Extinguisher.
|
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Mainline and Lighting disconnect shall be labeled with function and feeder breaker info.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Pit sump cover shall be able to safely withstand the weight of a worker with minimal deflection and allow proper water flow to sump.
|
|