Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 6/26/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Access to machine room shall be restricted to authorized personnel. Lock missing.
MO Minimum : Elevators (S) - Fire Service (S)1 x Doors will not open on Firefighters' Service Phase I recall. 6/26/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Elevator will not go to primary (main) level on Firefighters' Service Phase I recall. Goes to Floor 3. 6/26/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power is existing but was not tested. 8/23/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Lobby recall devices (smokes) recall elevator to incorrect landing. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 8.11.2.2.7 Standby power selector switch not working. 12/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 Seismic switch not working (ring and string)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10 Emegency Operation and Signaling Devices x RING AND STRING NOT WORKING, STILL 8/11/2022