Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Yes No "In Case of Fire" signage shall be provided in hallway at each landing
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 Yes No Air conditioning shall be installed and function to keep controllers at manufacturers recommended temperature.
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 Yes No Crosshead data plate shall be provided and engrave
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 Yes No Emergency Power / Standby power shall be tested
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 Yes No Hall Sill to hall floor presents a trip hazard on floors 1, M, 2, 4, 5,6,7,8,9,10,11,12,13. Hall floor shall be level with hall sill.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No Machine room floor has a large gap around the entire perimeter. Enclose floor to prevent trip hazard and prevent items from entering hoistway.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Machine room light switch shall be located at the point of entry
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No Machine room shall be 2 hour fire rated. Wood panels shall be removed.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No Machine room stairs do not allow for proper path and clearance to controllers. Handrail presents cut hazards. Remove homemade stairs and replace with ladder or stairs that do not impede access to controller and disconnects.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Yes No Machine room, car top, and pit need cleaned of construction dust, dirt, and debris
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Non-elevator related flex and electrical wiring shall be removed from the machine room.