Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Observed car emergency lighting not working. 3/3/2020
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Observed in-car alarm not working. 3/3/2020
conversion conversion n/a Door restrictor not working. 5/11/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Emergency power is existing but was not tested. 2/15/2021
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Car emergency lighting not working properly - bulb out. 2/15/2021
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Observed alarm bell not working when 110V removed. 2/15/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power is existing but was not tested. 3/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency lighting missing bulb and turns off and on when phone is activated. 3/23/2021
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.11.2.1.3(mm) Seismic switch (ring and string) not working. 5/19/2022
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x Suspension rope undersized. 6/5/2023