Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.4.1 No No Suspension ropes not equally tensioned. 5/1/2026
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.3.1.3(x) Yes No Suspension rope undersized. 4/14/2025
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.4.1 No No Suspension ropes not equally tensioned. 5/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) No No Emergency power indicator jewel in hall not working. 5/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) No No Emergency power indicator jewel in hall not working. 5/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Means of two way communication inoperable and shall be repaired or replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Water in pit (1”) 5/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Emer Power not tested. 4/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 No No Ring and string operation not working. 5/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm not working on normal power. 4/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting Yes No Emergency lights not working. 4/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 No No Standby power operation has not been tested. 5/1/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Standing water in pit. 5/1/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No No Category 5 tests performed/witnessed. 5/15/2024