Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car does not work on auxiliary power. Re-inspection required 12/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work on auxiliary power. Re-inspection required 12/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Provide and install test tags permanently marked with test data on all appropriate equipment
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required 12/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 There is a bottom guide roller on the counterweight that is cracked and shall be replaced.
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Hoistway access switches at top and bottom floors do not work to allow workers to safely access cartop and pit, repair same. Re-inspection required 12/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Hoistway access switches at top and bottom floors do not work to allow workers to safely access car top and pit, needs repaired. Re-inspection required